TPS system security policy (1) After installing the NT and TPS system software, enter the system as an Administrator. Create a new user Operator in Start → Programs → Administrative Tools, set it as the Administrator groups group in the selected group, and set it as the backup file and directory in the user permissions rule. Round Male Pin Header Connectors Round Male Pin Header Connectors,Straight Pin Male Pin Header Connectors,Straight Male Pin Header Connectors,Pitch Pin Connector Dongguan ZhiChuangXing Electronics Co., LTD , https://www.zcxelectronics.com
(2) Enter the system as Operator, and create the shortcut key of the user flowchart Main.pct in Start → Program → Settings → Taskbar → Start Menu → Advanced → Start Menu (if GUS operation station, then build a Native window The shortcut key).
(3) Run Regedit.exe, the registry editor program, in the Start → Run box. Open HKEY_CURRENT_USER\Software\current in Registry Editor
The Version\Policies\Explorer subkey branch, in which the Opertor user's system environment settings are completed. This is done by creating a new REG_DWORD type key item data.
Create a new REG_DWORD type key item data NoClose, and set its key value to 1. The function is: Block the "Turn off computer" option in the "Start" menu.
Create a new REG_DWORD key item data NoCommonGroups, and set its key value to 1. The function is: Block the common submenu of "Program" under the "Start" menu.
Create a new REG_DWORD type key item data NoRun, and set its key value to 1. The function is: mask the Run menu in the Start menu.
Create a new REG_DWORD type key item data NoFind, and set its key value to 1. The function is: Mask the "Search" menu in the "Start" menu.
Create new REG_DWORD type key item data NoSetFolders, NoContrdPanel, NoNetWorkConnection, NoSetTaskbar, and set its key value to 1. The function is: Mask the options in the "Settings" menu in the "Start" menu.
Create a new REG_DWORD type key item data NoWindowsUpdate, and set its key value to 1. The function is: mask the "Windows Update" option in the "Start" menu.
Create a new REG_DWORD key item data NoRecentDocsMenu, and set its key value to 1. The function is: mask the "document" option in the "Start" menu.
Create a new REG_DWORD type key item data NoSMHelp, and set its key value to 1. The function is: Mask the "Help" option in the "Start" menu.
Create a new REG_DWORD type key item data NoDeskTop, and set its key value to 1. The function is: mask all desktop icons.
Create a new REG_DWORD key item data NoViewContextMenu, and set its key value to 1. The function is: The right mouse button function is disabled.
Here you can make various edits according to your own needs.
(4) Exit the Operator identity, enter the system as Administrator, remove the Operator from the Administrator Groups group, replace it with the TPS View Only Groups group (if the GUS operation station, select TPS Operator Groups); change the user permissions rules of the Operator Start locally.
Restart the computer and enter the system as an Operator. The icon on the desktop disappears. Only the user's main flowchart, the Native Window window, and the note can be run on the Start menu. The operator can click the shortcut key of the user's main flow chart to enter the flow chart overview screen, and then perform various flow chart calls from the flow chart overview screen; if the GUS operation station can click the Native Window shortcut key to enter the Native Window window.